Part Number Hot Search : 
BCM5848U PTGT5 OM4215SW GP1006 TLE42 NJM2710V 4LVX1 240128
Product Description
Full Text Search
 

To Download LF205-S06 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Current Transducer LF 205-S
For the electronic measurement of currents : DC, AC, pulsed..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN
=
200 A
16135
Electrical data
IPN IP RM Primary nominal r.m.s. current Primary current, measuring range Measuring resistance @ with 12 V with 15 V ISN KN VC IC @ 200 A max @ 420 A max @ 200 A max @ 420 A max 200 0 .. 420 TA = 70C TA = 85C RM min RM max RM min RM max 0 0 0 0 71 14 100 28 0 0 23 23 69 12 98 26 A A
Features
* Closed loop (compensated) current
transducer using the Hall effect
mA V mA
* Insulated plastic case recognized
according to UL 94-V0.
Advantages
* * * * * * *
Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference * Current overload capability.
Secondary nominal r.m.s. current Conversion ratio Supply voltage ( 5 %) Current consumption @ 15 V
100 1 : 2000 12 .. 15 17 + I S
Accuracy - Dynamic performance data
XG
L
Overall accuracy @ IPN , TA = 25C Linearity error
0.5 < 0.1
% % mA mA mA ns s A/s kHz
IO IOM IO T tra tr di/dt f
Typ Max Offset current @ IP = 0, TA = 25C 0.2 Residual current 1) @ IP = 0, after an overload of 3 x IPN 0.1 Thermal drift of IO - 40C .. + 85C 0.12 0.4 Reaction time @ 10 % of IPN Response time 2) @ 90 % of IPN di/dt accurately followed Frequency bandwidth (- 3 dB) < 500 <1 > 100 DC .. 100
Applications
* AC variable speed drives and servo
motor drives
* Static converters for DC motor drives * Battery supplied applications * Uninterruptible Power Supplies
(UPS)
General data
TA TS RS m Ambient operating temperature Ambient storage temperature Secondary coil resistance @ TA = 70C @ TA = 85C Mass Standards - 40 .. + 85 C - 40 .. + 90 C 33 35 78 g EN 50178 : 1997
* Switched Mode Power Supplies
(SMPS)
* Power supplies for welding
applications.
Application domain
* Industry.
Notes :
1) 2)
The result of the coercive field of the magnetic circuit With a di/dt of 100 A/s.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060522/11
Page 1/3
LEM
w w w .lem.com
Current Transducer LF 205-S Isolation characteristics
Vd Vw Ve dCp dCl CTI R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn Impulse withstand voltage 1.2/50 s R.m.s. voltage for partial discharge extinction @ 10pC Creepage distance Clearance distance Comparative Tracking Index (Group III a) 3.5 8.8 >2 Min 11 10.2 175 kV kV kV mm mm
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions :
* Over voltage category OV 2 * Pollution degree PD3 * Non-uniform field
EN 50178 dCp, dCI, Vw Single isolation Reinforced isolation Rated isolation voltage 500 V 250 V
IEC 61010-1 Nominal voltage 500 V 250 V
Safety
This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions.
Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected.
060522/11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 2/3
LEM
w w w .lem.com
Dimensions LF 205-S
(in mm. 1 mm = 0.0394 inch)
Bottom view
Right view
Front view
Back view
Connection Top view
Mechanical characteristics
* General tolerance * Transducer fastening
Vertical position Fastening torque, max or 0.2 mm 2 holes 4.3 mm 2 M4 steel screws 3.2 Nm or 2.37 Lb. - Ft. 4 holes 1.9 mm depth 7 mm 4 x PT KA25 screws long 6 mm 4 holes 4.3 mm 4 M4 steel screws 3.2 Nm or 2.37 Lb. - Ft. 4 holes 1.9 mm 4 x PT KA25 screws 0.7 Nm or 0.52 Lb. - Ft. 15.5 mm Molex 5045-0.3/A
Remarks
* IS is positive when IP flows in the direction of the arrow. * Temperature of the primary conductor should not exceed
100C.
* Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
* This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...), please contact us.
* Transducer fastening
Horizontal position Fastening torque, max or Fastening torque, max
* Primary through-hole * Connection of secondary LEM
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060522/11
Page 3/3
w w w .lem.com


▲Up To Search▲   

 
Price & Availability of LF205-S06

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X